Grounding Transformers

Grounding is clearly one of the most important aspectstransformer offers many safety improvements over
of electrical design, but it steadfastly continues to bean ungrounded system. However, the ground
misinterpreted and misunderstood. Millions of dollars intransformer alone lacks the current limiting ability of a
liability and loss can be attributed to ground-fault arcing;resistive grounding system. For this reason, neutral
thus, grounding-related issues should top the checklistsground resistors are often used in conjunction with the
of any electrical contractor.grounding transformer to limit neutral ground fault
Grounding Transformers:current magnitude. Their ohm values should be
Simply put, a grounding transformer is used to providespecified to allow high enough ground fault current flow
a ground path to either an ungrounded "Y" or a deltato permit reliable operation of the protective relaying
connected system. Grounding transformers areequipment, but low enough to limit thermal damage.
typically used to:How to Specify a Grounding Transformer
1. Provide a relatively low impedance path to ground,The basic parameters required for quoting a grounding
thereby maintaining the system neutral at or neartransformer are:
ground potential- Primary Voltage - This is the system voltage to
2. Limit the magnitude of transient over voltages whenwhich the grounded winding is to be connected. Don't
re-striking ground faults occurforget to specify the BIL also. In some cases the BIL
3. Provide a source of ground fault current duringwill be dictated by equipment considerations, such as
line-to-ground faults150 kV BIL ratings on 34500 volt wind farms because
4. Permit the connection of phase to neutral loadsof the limitation on dead front connectors.
when desired- Rated KVA - Because the grounding transformer is
If a single line-to-ground fault occurs on an ungroundednormally a short time device, its size and cost are less
or isolated system, no return path exists for the faultwhen compared with a continuous duty transformer of
current, thus no current flows. The system will continueequal kVA rating. For this reason, grounding
to operate but the other two un-faulted lines will rise intransformers are often not sized by "kVA" but by their
voltage by the square root of 3, resulting incontinuous and short time current ratings. Regardless
overstressing of the transformer insulation and otherof how you rate it, the grounding transformer must be
associated components on the system by 173%. MOVsized to carry the rated continuous primary phase
lightning arresters are particularly susceptible tocurrent without exceeding its temperature limit. This
damage from heating by leakage across the blocksload includes the magnetizing current of the core, the
even if the voltage increase is not sufficient to flashcapacitive charging current for the cables, and any
over. A grounding transformer provides a ground pathauxiliary load if applicable.  The higher this value, the
to prevent this.larger and more costly the transformer will be. 
Large multi-turbine wind farms provide an example ofTypical continuous current values can be as low as 5
the use of grounding transformers for fault protectionamps to as high as a few hundred. Be sure to include
on ungrounded lines. In many wind farms the substationany auxiliary loading requirements.
transformer provides the sole ground source for the- Continuous Neutral Current - The continuous neutral
distribution system. When a ground fault on a collectorcurrent is defined as three times the phase to current,
cable causes the substation circuit breaker for thator in other words, the zero sequence current. This is
cable to open, the wind turbine string becomes isolatedusually considered to be zero if the system is
from the ground source. The turbines do not alwaysbalanced. However, for the purposes of designing a
detect this fault or the fact that the string is isolatedgrounding transformer, it is a value that is expected to
and ungrounded; thus the generators continue toflow in the neutral circuit without tripping protective
energize the collector cable, and the voltages betweencircuits (which would force the current to be zero) or
the un-faulted cables and the ground rise far abovethe leakage current to ground that is not a symmetrical
the normal voltage magnitude as described above. Afunction. Again this value is needed to design for
grounding transformer placed on the turbine stringthermal capacity of the grounding transformer.
provides a ground path in the event the string- Fault current and duration - This value is needed to
becomes isolated from the system ground.calculate the short time heating that results from a
Construction:fault on the system and should be determined from an
Grounding transformers are normally constructedengineered system study. Typical values for this range
either withfrom a few hundred amps to a few thousand amps
1. A ZigZag (Zn) connected winding with or without anwith duration times expressed in seconds and not
auxiliary winding orcycles. For instance, a value of 400 amps for 10
2. As a Wye (Ynd) connected winding with a deltaseconds is typical. The fault duration is a critical
connected secondary that may or may not be usedparameter for the transformer designer. Where
to supply auxiliary powerprotection schemes use the grounding transformer for
The geometry of the Zig-Zag connection is useful totripping functions, a relatively short time duration is
limit circulation of third harmonics and can be usedspecified (5 -10 seconds). On the other hand, a
without a Delta connected winding or the 4- or 5-legcontinuous or extended neutral fault current duration
core design normally used for this purpose inwould be required when the grounding transformer is
distribution and power transformers. Eliminating theused in a ground fault alarm scheme.
need for a secondary winding can make this option- Impedance - The impedance can be expressed as a
both less expensive and smaller than a comparablepercentage or as an ohm value per phase. In either
two-winding grounding transformer. Furthermore, usecase it should be chosen so that the un-faulted phase
of a Zig-Zag transformer provides grounding with avoltages during a ground fault are within the temporary
smaller unit than a two-winding Wye-Delta transformerover-voltage capability of the transformer and
providing the same zero sequence impedance.associated equipment, such as arresters and terminal
Wye connected grounding transformers, on the otherconnectors. Because of this description, the values can
hand, require either a delta connected secondary orvary from as low as 8% to almost 100%. This value
the application of 4 or 5 leg core construction tomust come from the system designer.
provide a return flux path for unbalanced loading- Primary winding connection - Specify the type of
associated with this primary connection. Since it isprimary connection, either Zig-Zag or grounded Wye.
often desirable to provide auxiliary power from the- Secondary connection - specify the secondary
grounding transformer secondary winding, this benefitvoltage and connection when applicable.
can sway the end user to specify a two-windingSpecify the size of auxiliary loading to be connected
grounding transformer in lieu of a Zig-Zag connection.for either Zn or Wye connected primary windings.
The current trend in wind farm designs is toward theIf the option is to have a two winding transformer with
Wye connected primary with a delta secondary.no secondary load, advise if the delta winding can be
It is important to understand that both Zig-Zag and"buried" (that is not brought out) or if only one bushing is
two-winding grounding transformers can be providedto be brought out for grounding to the tank or testing.
with the ability to provide auxiliary power, and this can- Basic overall construction features - note the
be either a Wye or Delta connected load.following features as they apply to each transformer...
A solidly grounded system using a grounding